Start Prevented
Vacon · 100 FLOW Application Guide
Hva betyr 76 ?
The drive's start command has been blocked, primarily to prevent accidental motor rotation, especially during the initial power-up sequence. This is a safety feature to ensure the system is in a known, safe state before operation. The drive will not operate until this prevention is cleared.
Vanlige årsaker
- An active safety interlock signal (e.g., Safe Torque Off via terminals STO1/STO2) is preventing motor start.
- The drive is in a fault state and requires a fault reset before a start command can be accepted (check status word P0-01).
- Parameter P1-11 (Auto Restart) is set to 'No' or 'Fault Reset Only', preventing automatic restart after power-up or fault.
- The speed reference command is zero, and the minimum speed parameter (P1-01) is set above zero, requiring a non-zero reference.
- External run command via digital input is not active, or a communication link (fieldbus) is not sending a valid run command.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
1. Verify the status of all safety inputs (e.g., STO terminals, emergency stop circuits) and ensure they are disengaged.
- 2
2. Check the drive's status word (P0-01) for any active faults and perform a fault reset if required.
- 3
3. Confirm the speed reference input (e.g., analog input terminal AI1 or fieldbus reference) is providing a non-zero value.
- 4
4. Review parameter P1-11 (Auto Restart) and adjust it if a different automatic start behavior is desired.
- 5
5. Measure the voltage across the digital input terminals configured for the run command (e.g., DI1 to GND) to confirm signal presence.
- 6
6. If using fieldbus, confirm the fieldbus master is actively sending a run command bit in its output data.