Too Many Active Connections
Vacon · 100 FLOW Application Guide
Hva betyr 77 ?
The drive has detected more than 5 active fieldbus or PC tool connections simultaneously. The system limits concurrent connections to a maximum of 5. Exceeding this limit can cause communication instability or prevent new connections.
Vanlige årsaker
- More than 5 simultaneous connections from PC tools (e.g., programming software, monitoring tools) to the drive's communication ports.
- Multiple fieldbus masters or controllers attempting to establish concurrent connections with a single drive.
- Network misconfiguration or a faulty fieldbus device causing persistent, phantom connections to remain active.
- A PC tool or fieldbus master connection was not properly terminated, leaving an active session open in the drive's memory.
- Drive firmware limitation or bug misinterpreting connection requests, leading to an inflated connection count.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
1. Identify and disconnect all non-essential PC tools (e.g., commissioning software, diagnostic tools) from the drive's communication ports.
- 2
2. Review the fieldbus network topology to ensure only one fieldbus master is configured to communicate with the drive.
- 3
3. Power cycle the drive and any connected fieldbus masters or HMI panels to clear all active communication sessions.
- 4
4. Use a network monitoring tool (if applicable) to identify the source of multiple connection attempts to the drive's IP address or node ID.
- 5
5. Verify the drive's communication parameters (e.g., P4-00 for fieldbus type, P4-99 for communication diagnostics) for any errors or abnormal settings.
- 6
6. Check if any remote access software or SCADA systems are maintaining persistent, unneeded connections to the drive.