The frequency converter has detected a motor current exceeding four times the nominal current (>4*IN) in the motor cable. This condition typically results from a sudden heavy increase in motor load, a short circuit in the motor cables, or the use of an unsuitable motor for the application, posing a risk of damage to the motor or drive.

Vanlige årsaker

  • Motor draws excessive current.
  • Short circuit in motor windings or cables.
  • Mechanical overload or jamming.
  • Rapid acceleration or deceleration ramps (P1-16, P1-17).
  • Output voltage too low relative to motor speed.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the motor loading to ensure it is within the rated capacity of the drive and motor.

  2. 2

    Verify the motor size matches the application requirements and the frequency converter specifications.

  3. 3

    Inspect all motor cables for any signs of physical damage, insulation breakdown, or short circuits between phases or to ground.