Overcurrent

Vacon · NX All-in-One Application

Hva betyr 1 ?

A hardware trip (S1) has detected excessively high current (>4 times nominal current) in the motor cable, potentially due to a sudden heavy load, a short circuit in the motor cables, or an incorrectly matched motor. Other subcodes (S3, S4) indicate current controller supervision issues or an exceeded user-configured limit.

Vanlige årsaker

  • Motor or load current exceeds the nominal rating (e.g., P1-10 = 15A).
  • Short circuit in the motor windings or power cables.
  • Mechanical overload on the driven equipment.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Inspect the motor's mechanical loading and reduce if exceeding the motor's nominal capacity.

  2. 2

    Verify the motor's specifications (e.g., nominal current, voltage, power) match the AC drive's rating and application requirements.

  3. 3

    Visually inspect the motor cables for damage, proper routing, and verify all connections are secure and free of short circuits.

  4. 4

    Perform an identification run to ensure the drive's motor parameters are accurately tuned to the connected motor.

Se alle koder i denne manualen (42)