57
Identification Run Failed
Vacon · NX Liquid-Cooled Drive
Hva betyr 57 ?
The motor identification run has failed. This can occur if the run command was prematurely removed before the identification process completed, if the motor is not properly connected to the AC drive, or if there is a mechanical load on the motor shaft during the identification sequence which should be performed without load.
Vanlige årsaker
- Motor auto-identification process failed to complete successfully.
- Incorrect motor parameters for identification (P0201).
- Motor not properly connected or spinning freely during identification.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Ensure the run command remains continuously active throughout the entire duration of the identification run.
- 2
Verify that the motor is correctly and securely connected to the AC drive's output terminals (U, V, W).
- 3
Ensure there is no mechanical load on the motor shaft during the identification run; disconnect any loads if necessary.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Vacon NX Liquid-Cooled Drive