18

Unbalance

Vacon · NXS NXP

Hva betyr 18 ?

An unbalance has been detected between power modules within paralleled power units. This signifies a discrepancy in current sharing or performance among the modules, which can lead to uneven wear and a reduced lifespan of the power components. If persistent, this fault indicates an internal issue within the paralleled power system.

Vanlige årsaker

  • Uneven impedance or resistance in output cabling (U, V, W) between parallel power modules and the common motor.
  • Faulty current sensor or measurement circuit within one of the paralleled power modules causing inaccurate current feedback.
  • Mismatched firmware versions or parameter settings (e.g., P5-10 "Parallel control mode") between the paralleled power modules.
  • Degradation or failure of switching components (IGBTs) in one power module, leading to poor current regulation.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify uniform length and gauge of output cables (U, V, W) from each power module to the common motor connection point.

  2. 2

    Check for loose or corroded connections on output terminals (U, V, W) and input terminals (R, S, T) of each power module.

  3. 3

    Compare current feedback values (e.g., P0-01) from each individual power module using a multimeter with a current clamp or through the drive's display.

  4. 4

    Confirm all paralleled power modules have identical firmware versions and critical parallel control parameters (e.g., P5-10, P5-11, P5-12) are correctly configured.

  5. 5

    Isolate each power module, if possible, and run independently to identify which module exhibits abnormal current draw or output.

Se alle koder i denne manualen (54)
Verifisert teknisk data. Sist oppdatert: March 2026