MOL Contact Fault
Vacon · X4
Hva betyr 7 ?
This fault occurs when the Motor Overload (MOL) digital input is activated, indicating an overload condition detected externally or a misconfiguration of the input logic. The MOL input acts as a safety interlock to protect the motor from damage due to excessive thermal or current loading.
Vanlige årsaker
- External motor overload relay (connected to the MOL input) tripped due to an actual motor overload condition.
- Incorrect configuration of the digital input assigned as MOL (e.g., parameter P0-19 DI Function) resulting in unintended activation.
- Open circuit in the wiring to the MOL digital input, if configured as a normally closed (NC) contact.
- Faulty external overload relay or wiring causing a false trip signal to the MOL input.
- Contactor chatter or auxiliary contact bounce triggering the MOL input intermittently.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
1. Inspect the external motor overload relay (thermal or electronic) for a tripped status indicator and reset it if necessary.
- 2
2. Verify parameter P0-19 (DI Function) or similar parameter for the MOL input is correctly configured for the desired normally open (NO) or normally closed (NC) logic.
- 3
3. Measure the continuity of the external MOL contact and its wiring back to the drive's digital input terminal to ensure a proper signal path.
- 4
4. Check the motor's actual current draw using a clamp meter at the drive output (T1/U, T2/V, T3/W) to determine if a true overload condition exists (compare to P0-03).
- 5
5. Temporarily bypass the MOL input by removing its wiring from the drive terminal (ensure safety procedures are followed) to confirm if the fault clears.