Insufficient configuration data (Fault code 3, argument 1)

Wago · Modular I/O System PROFIBUS DP

Hva betyr BUS-LED 3-1 ?

The Fieldbus Coupler has insufficient configuration data, most likely because an I/O module was overlooked during the configuration process. This prevents the coupler from fully recognizing and operating all connected modules, leading to incomplete system functionality.

Vanlige årsaker

  • A specific I/O module was omitted from the configuration
  • The loaded configuration data is incomplete for the physically connected modules

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the configuration to verify all physical modules are included.

  2. 2

    Load the corrected configuration onto the coupler.

  3. 3

    Cycle the supply voltage of the coupler (off then on again) to restart.

Se alle koder i denne manualen (21)
Verifisert teknisk data. Sist oppdatert: March 2026