BUS-LED 3-2

Excessive configuration data (Fault code 3, argument 2)

Wago · Modular I/O System PROFIBUS DP

Hva betyr BUS-LED 3-2 ?

The Fieldbus Coupler has excessive configuration data, possibly due to a module being incorrectly configured multiple times or redundant data entries. This can result in configuration mismatches and operational issues, impacting coupler and module functionality.

Vanlige årsaker

  • A specific I/O module was incorrectly included multiple times in the configuration
  • The loaded configuration data contains redundant or erroneous entries

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the configuration for any redundant or incorrect module entries.

  2. 2

    Load the corrected configuration onto the coupler.

  3. 3

    Cycle the supply voltage of the coupler (off then on again) to restart.