Yaskawa · A1000

Hva betyr oPE12 ?

The energy savings feature was enabled while the Output Voltage PID function was also active. This condition typically arises when parameter b8-01 (Energy Save) is set to 'Enable' (1) at the same time parameter P1-08 (Output Voltage PID Select) is set to 'Enabled' (1), and the drive's control method (A1-02) is configured for V/f operation.

Vanlige årsaker

  • Parameter b8-01 (Energy Save) is set to 'Enable' (1)
  • Parameter P1-08 (Output Voltage PID Select) is set to 'Enabled' (1)
  • The drive's control method (A1-02) is configured for V/f operation (0) concurrently with the above conditions

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Set parameter b8-01 (Energy Save) to 'Disable' (0)

  2. 2

    Alternatively, set parameter P1-08 (Output Voltage PID Select) to 'Disabled' (0)