Undertorque Detection 2
Yaskawa · F7 Drive
Hva betyr UL4 ?
Similar to UL3, this fault indicates the drive's output current was below the L6-05 threshold for longer than L6-06, with L6-04 set for undertorque detection. It signifies a motor running under an unexpectedly light load condition, potentially indicating a process issue or mechanical failure that needs investigation.
Vanlige årsaker
- Mechanical decoupling of the motor from its load (e.g., broken shaft, slipped coupling, loss of fluid in a pump).
- Process material flow stoppage or significant reduction in demand (e.g., valve closure, fan duct blockage).
- Undertorque detection level (L6-05) set too high for the second detection stage's intended low-load scenario.
- Undertorque detection delay time (L6-06) set too short, leading to nuisance trips for brief current dips.
- Temporary drop in system pressure or flow, causing the motor to momentarily operate at a lighter load.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
1. Visually inspect the driven equipment for signs of mechanical load loss, such as a broken shaft, slipped coupling, or loss of fluid in a pump.
- 2
2. Observe the process for any conditions that would naturally lead to a sustained reduction in motor load and current draw.
- 3
3. Use a clamp-on ammeter to accurately measure the motor's actual output current under the specific light-load conditions intended for UL4 detection.
- 4
4. Adjust parameter L6-05 (Undertorque Detection Level 2) to a value below the measured minimum operating current for the expected light-load scenario.
- 5
5. Increase parameter L6-06 (Undertorque Detection Time 2) to provide a longer delay, preventing immediate fault trips during brief current dips.