Oversetter...
UV

Undervoltage Alarm

Yaskawa · F7 Drive

Hva betyr UV ?

An Undervoltage (UV) alarm is displayed on the digital operator during a momentary power loss event, specifically after power loss but before a fault trip occurs. This indicates that the drive is actively attempting to ride through the power loss, maintaining operation as long as control power is sustained. It's a warning, not a fault that stops the drive immediately.

Vanlige årsaker

  • Momentary dip or sag in the incoming AC line voltage (L1/R, L2/S, L3/T) lasting longer than typical grid noise but not severe enough to cause a hard fault.
  • Heavy load transients on the power grid causing temporary voltage reductions that activate the undervoltage alarm threshold.
  • Poorly regulated power supply or undersized distribution transformer feeding the drive, leading to voltage fluctuations.
  • Loose or corroded connections in the main power circuit before the drive, causing voltage drops under load.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Monitor the incoming AC line voltage at the drive's L1/R, L2/S, L3/T terminals with a power quality analyzer to identify voltage dips or sags.

  2. 2

    Verify the ride-through capabilities of the drive by checking parameters related to power loss compensation (e.g., L2-01, L2-02, L2-03, L2-04), ensuring they are optimized for the application.

  3. 3

    Inspect all main power wiring connections, from the facility's main disconnect to the drive's input, for tightness and corrosion.

  4. 4

    If the problem is widespread, consult the facility's electrical engineer to assess the main power distribution system and transformer sizing.

  5. 5

    Consider installing an Uninterruptible Power Supply (UPS) for the control circuit or a line reactor on the input of the drive to mitigate voltage fluctuations.

Se alle koder i denne manualen (63)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder