UV1

DC Bus Undervoltage

Yaskawa · F7 Drive

Hva betyr UV1 ?

The DC bus voltage inside the drive has fallen below the trip point (e.g., 190Vdc for 240V AC input or 380Vdc for 480V AC input), which is adjustable via L2-05. Common causes include insufficient incoming AC power, excessively short acceleration times leading to voltage sag, or significant fluctuations in the input voltage quality.

Vanlige årsaker

  • Insufficient incoming AC line voltage to the drive's L1/R, L2/S, L3/T terminals, possibly due to grid instability or undersized supply transformer.
  • Momentary power loss or sag in the main AC supply, causing the DC bus capacitors to discharge below the undervoltage trip level (L2-05).
  • Faulty or worn pre-charge resistors/circuitry failing to adequately charge the DC bus capacitors.
  • Damaged DC bus capacitors or internal power supply components within the drive, leading to reduced voltage holding capacity.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the incoming AC line voltage at the drive's L1/R, L2/S, L3/T terminals using a multimeter to confirm it is within 10% of the drive's nominal input voltage.

  2. 2

    Verify the parameter L2-05 (DC Bus Undervoltage Detection Level) is set correctly according to the drive's nominal input voltage (e.g., 190V for 240V drive or 380V for 480V drive).

  3. 3

    Inspect the wiring connections from the main power supply breaker to the drive's input terminals (L1/R, L2/S, L3/T) for loose connections or corrosion.

  4. 4

    Monitor the DC bus voltage (dC bus monitor value) on the drive's operator panel during operation to observe its behavior relative to the L2-05 trip point.

  5. 5

    If a dynamic braking unit is present, verify its functionality by checking for continuity across the braking resistor terminals and proper connection to the drive (B1, B2).

Se alle koder i denne manualen (63)