Oversetter...
dv7

Polarity Judge Timeout

Yaskawa · GA500 Maintenance and Troubleshooting

Hva betyr dv7 ?

The drive failed to detect motor polarity within the preset time, indicating an issue with the motor's electrical connection or winding integrity. This can prevent proper motor startup, accurate current control, and safe operation.

Vanlige årsaker

  • Open phase or high resistance in one or more motor windings (U, V, W).
  • Motor cable disconnection or poor terminal contact at either the drive (U, V, W output) or the motor.
  • Incorrect motor wiring configuration (e.g., Delta/Wye) not matching the motor's operating voltage.
  • Internal short circuit or ground fault within the motor windings.
  • Incorrect motor auto-tuning parameter (e.g., L3-01 [Motor Auto-tuning Select]) preventing successful polarity detection.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Power down the drive, disconnect motor cables (U, V, W) from the drive.

  2. 2

    2. Measure resistance between motor terminals U-V, V-W, and W-U; readings should be balanced (e.g., within 5%).

  3. 3

    3. Measure insulation resistance from each motor terminal (U, V, W) to motor frame ground using a megohmmeter (e.g., 500VDC).

  4. 4

    4. Verify all motor cable connections at both the drive and motor are tight and clean.

  5. 5

    5. Ensure the motor is not mechanically locked or excessively stiff, preventing rotation during the polarity test.

  6. 6

    6. Confirm motor type parameters (e.g., P2-04 [Motor Rated Power], P2-06 [Motor Poles]) are set correctly before attempting auto-tuning.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Yaskawa GA500 Maintenance and Troubleshooting
Yaskawa dv7 (Polarity Judge Timeout) — Teknisk referanse | ErrorLib