External Fault (Terminal S2)
Yaskawa · GA500 Maintenance and Troubleshooting
Hva betyr EF2 ?
An external fault signal was received via MFDI terminal S2, possibly due to a problem with the connected external device, faulty wiring, or a misconfiguration where parameter H1-02 is set for an external fault (range 20 to 2F) but the terminal is not actively utilized. This will cause the drive to trip and stop the motor, potentially disrupting the process.
Vanlige årsaker
- External device connected to MFDI terminal S2 (e.g., E-stop button contact) is active, signaling a fault condition.
- Damaged or loose wiring connection between the external device and MFDI terminal S2.
- Parameter H1-02 is incorrectly set to "External Fault" when S2 should perform a different function.
- Transient voltage spike or ground loop causing an erroneous signal on the S2 input.
- Faulty relay contact or sensor output connected to S2.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
1. Measure the voltage potential between MFDI terminal S2 and the common terminal (e.g., SN, S+) to determine its state.
- 2
2. Verify the status of the external device connected to S2 (e.g., E-stop relay, pressure switch).
- 3
3. Check parameter H1-02 to confirm it is correctly assigned for the intended S2 function.
- 4
4. Disconnect the wire from MFDI terminal S2 and observe if the EF2 fault clears.
- 5
5. Inspect the wiring from the external device to S2 for damage, loose connections, or proper shielding.
- 6
6. Temporarily configure parameter H1-02 to a non-fault function to rule out internal drive issue with S2 input.