Oversetter...
MSL
Net Master Lost
Yaskawa · iQpump1000
Hva betyr MSL ?
The MEMOBUS master has been lost, meaning no message has been received from the master within the time set in P9-26. This fault occurs when P9-27 (Network Recovery) is set to 3 (Fault MSL).
Vanlige årsaker
- No message received from the master within the time set in P9-26.
- Network Recovery (P9-27) is set to 3 (Fault MSL).
- Faulty network connections.
- Incorrect H5-01 or P9-25 settings on network drives.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Increase the P9-26 setting to account for network latency.
- 2
Verify that a drive on the network has parameter P1-01 set to 3 and P9-27 set to 0 to act as a master.
- 3
Check network connections for integrity.
- 4
Verify H5-01 and P9-25 settings for all drives on the network are correct.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Yaskawa iQpump1000