VLTS

Volute-Thermostat Fault

Yaskawa · iQpump1000

Hva betyr VLTS ?

This fault occurs when a digital input assigned to the volute/thermostat input (H1-0o = 88 or 89) is active, or if both volute/thermostat inputs are programmed simultaneously. Auto-restart is controlled by parameter L5-53.

Vanlige årsaker

  • The digital input assigned to the volute/thermostat input (H1-0o = 88 or 89) is active
  • Both volute/thermostat inputs are programmed simultaneously (H1-0o = 88 and 89)

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the wiring to the volute or motor thermostat

  2. 2

    Allow the volute or motor to cool

  3. 3

    Program only one digital input to either H1-0o = 88 or H1-0o = 89

  4. 4

    Review parameter L5-53 (Volute-TStat Retry Selection) for auto-restart settings