Oversetter...
oL3

Overtorque 1

Yaskawa · J1000

Hva betyr oL3 ?

The drive's output current (or calculated torque in OLV, CLV, AOLV/PM, CLV/PM modes) has exceeded the threshold set in L6-02 for longer than the time specified in L6-03. This fault typically indicates either incorrect parameter settings for torque detection or a mechanical issue on the machine side causing excessive load on the motor. Ignoring this can lead to damage to the motor, gearbox, or driven equipment.

Vanlige årsaker

  • Mechanical jamming or obstruction in the driven load requiring excessive torque.
  • Sudden increase in load demand beyond the motor's or drive's capacity.
  • Incorrect setting of parameter L6-02 (Overtorque 1 Detection Level) too low.
  • Incorrect setting of parameter L6-03 (Overtorque 1 Detection Time) too short.
  • Motor undersized for the peak torque requirements of the application.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Inspect the mechanical system (e.g., gearbox, conveyor) for signs of jamming, binding, or unusual resistance.

  2. 2

    Measure the drive's output current (A) during typical operation and during the overtorque event.

  3. 3

    Review parameter L6-02 (Overtorque 1 Detection Level) and L6-03 (Overtorque 1 Detection Time); adjust based on load.

  4. 4

    Verify motor parameters (P1-01 to P1-08) are correctly entered for accurate torque estimation.

  5. 5

    Check for sudden load changes or shock loads during the operating cycle that might momentarily exceed the limit.

  6. 6

    Compare the motor's rated torque (Nm) to the peak torque required by the application.

Se alle koder i denne manualen (59)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder