A/D Conversion Fault
Yaskawa · P1000
Hva betyr CPF22 ?
A fault occurred within the analog-to-digital conversion circuitry of the drive. This affects the accuracy of input signal readings from sensors and other analog sources.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Inspect all analog input wiring (signal and return) for proper shielding, secure connections, and absence of damage or corrosion at both the sensor and drive terminals.
- 2
Measure the actual analog input signal (e.g., voltage or current) directly at the drive's input terminals using a multimeter or oscilloscope, and compare to expected values and stability.
- 3
Verify drive parameters related to analog input configuration, scaling, offset, and filtering (e.g., A1-xx for P1000) match the connected sensor type and desired application.
- 4
Inspect the drive's control power supply grounding and the integrity of the overall panel grounding connections to minimize potential noise or interference.