oL7

High Slip Braking Overload

Yaskawa · P1000

Hva betyr oL7 ?

An overload condition occurred during high slip braking, indicating excessive regenerative energy or an issue with the braking process. This can lead to component overheating.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify drive parameters related to deceleration time (e.g., P2-xx) and braking resistor operation (e.g., P6-xx series) against application requirements and specifications.

  2. 2

    Inspect the external braking resistor (if installed) and its wiring connections to the drive terminals (+1/+2) for any damage, loose terminals, or signs of overheating.

  3. 3

    Measure the resistance value of the external braking resistor (with power off and discharged) and compare it against the specified ohmic rating.

  4. 4

    Observe the mechanical load and deceleration profile during operation to identify excessive inertia or overly aggressive deceleration rates causing regenerative conditions.