Oversetter...
Overcurrent

Overcurrent Trip

Yaskawa · V1000

Hva betyr Overcurrent ?

An excessive current flow has been detected at the drive's output. This is typically caused by a short circuit or ground fault on the output side, an extremely heavy mechanical load, overly short acceleration/deceleration times, incorrect motor data, or switching a magnetic contactor at the output. This condition can severely damage the drive's power section (IGBTs).

Vanlige årsaker

  • Short circuit between two output phases (U, V, W) or a ground fault on the drive's output wiring or motor windings.
  • Excessively heavy mechanical load on the motor, causing the motor to draw current beyond the drive's instantaneous overcurrent threshold.
  • Acceleration time (Parameter C1-01) or deceleration time (Parameter C1-02) is set too short for the inertia of the connected load.
  • Motor stalled due to mechanical binding or blockage in the driven equipment.
  • Drive output current limit (Parameter C2-01) is set too low for the application's peak current demands.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. De-energize the drive and disconnect the motor; perform an insulation resistance test (megohmmeter) on each output phase (U, V, W) to ground and between phases to check for short circuits.

  2. 2

    2. Check for mechanical binding or obstruction in the driven load that could be causing excessive torque requirements.

  3. 3

    3. Increase the acceleration time (Parameter C1-01) and deceleration time (Parameter C1-02) by 20% increments.

  4. 4

    4. Verify motor nameplate current against the drive's rated output current to ensure proper sizing.

  5. 5

    5. Monitor drive output current (via display or software) during start-up to identify when the overcurrent condition occurs relative to motor speed.

  6. 6

    6. Adjust the drive's current limit (Parameter C2-01) if necessary, ensuring it remains within safe operating limits for the motor and drive.

Se alle koder i denne manualen (87)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder