SI-B Communication Error
Yaskawa · VS-616G5 Variable Speed Drive
Hva betyr BUS ?
This fault occurs when using the SI-B or CP-916 communication options if communication is lost after being established. It signifies a disruption in communication with the option card, which can halt control functions or data exchange, leading to operational stoppage and loss of control.
Vanlige årsaker
- Loose or damaged communication cable (e.g., Cat5e, RS-485) between the inverter and the SI-B/CP-916 card or master device.
- Incorrect termination resistor setting on the SI-B/CP-916 card or the communication bus line.
- Electromagnetic interference (EMI) disrupting the communication signal due to improper cable shielding or grounding.
- Faulty SI-B or CP-916 communication option card requiring replacement.
- Incorrect communication parameters (e.g., baud rate, parity, data bits, station address) configured in P5-XX range (for SI-B) or CP-916 card settings.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify physical connections of the communication cable (e.g., terminals TB1/TB2 for RS-485) at both the inverter SI-B/CP-916 card and the master device.
- 2
Measure the communication cable continuity and insulation resistance using a multimeter to detect breaks or shorts.
- 3
Confirm correct termination resistor switch (SW1) setting on the SI-B/CP-916 card (ON for end devices, OFF for middle devices).
- 4
Check communication parameters (e.g., P5-01, P5-02, P5-03 for SI-B) in the inverter and the master device for matching values.
- 5
Inspect the SI-B/CP-916 option card for visible damage and test with a known good card if available.