Signal level too low
SEW Eurodrive · MOVIDRIVE system
What does F14.6 mean?
The signal level from Encoder 2 is too low, falling below the permitted limit during monitoring. This indicates a problem with the wiring, external electromagnetic interference (EMC), or a faulty encoder, leading to unreliable position feedback.
Common Causes
- Degradation or damage to the Encoder 2 signal cables (e.g., incremental A/B/Z signals or Sin/Cos signals) leading to increased resistance or partial open circuits.
- Inadequate shielding of the Encoder 2 cable, allowing external electromagnetic interference (EMI) to attenuate the signal.
- Internal failure of the Encoder 2 output driver circuitry, resulting in reduced signal amplitude.
- Incorrect termination resistance (P3-60) for the encoder signals on the drive input card X2, leading to signal reflection and attenuation.
- Loose connection at the Encoder 2 connector or at the drive's input terminal X2 causing poor contact.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Measure the differential voltage of the Encoder 2 signals (e.g., A+ to A-, B+ to B-) at drive terminal X2 using an oscilloscope, observing peak-to-peak amplitude.
- 2
Inspect the entire length of the Encoder 2 cable for cuts, abrasions, or crushed sections, focusing on the signal conductors.
- 3
Verify the encoder cable shielding is properly terminated at both the encoder and drive ends (grounded).
- 4
Check drive parameter P3-60 (Encoder 2 termination resistance) and adjust according to the encoder's specified output characteristics.
- 5
Clean and re-seat the Encoder 2 cable connector at both the encoder and drive input terminal X2.