FF89
MOD CHOKE T
ABB · ACS560 Standard Control Program Firmware
What does FF89 mean?
Overtemperature has occurred in the choke of a liquid-cooled R8i inverter module. Excessive heat in the choke can reduce its magnetic properties and potentially lead to insulation breakdown, compromising drive performance and safety.
Complete Troubleshooting Guide
- 1
Check the inverter fan(s) for proper operation, ensuring they are rotating freely and providing adequate airflow.
- 2
Verify the ambient temperature around the inverter, ensuring it is within the specified operating limits.
- 3
Inspect the liquid cooling system for proper flow, leaks, and coolant level, as well as condition of heat exchangers.