3381
Output phase loss
ABB · ACS580 General Purpose Drive
What does 3381 mean?
The drive has detected a loss of one or more phases between its output terminals and the connected motor. This typically results from a broken cable, loose connection, or open circuit protection, which can lead to motor instability, overheating, or failure if ignored.
Complete Troubleshooting Guide
- 1
Physically inspect all motor connections from the drive output terminals to the motor.
- 2
Check the continuity of the motor cables for each phase using a multimeter.
- 3
Verify the integrity and state of any contactors, fuses, or disconnects in the motor circuit.
- 4
Measure motor winding resistance to ensure the motor itself is not open-phased.