What does 6681 mean?
A communication break has occurred in the embedded fieldbus (EFB) communication link. This means the drive has lost its connection with the fieldbus master, leading to a loss of control and monitoring capabilities via the EFB, which can halt automated processes.
Complete Troubleshooting Guide
- 1
Check the operational status of the fieldbus master (e.g., online, offline, error status).
- 2
Inspect all physical cable connections to the EIA-485/X5 terminals 29, 30, and 31 on the control unit for secure and correct wiring.
- 3
Verify termination resistors and addressing on the fieldbus network.