7191

BC short circuit

ABB · ACS580 General Purpose Drive

What does 7191 mean?

A short circuit has been detected within the brake chopper circuit, specifically occurring when an earth fault condition is also present and the brake chopper is active. This is a severe fault that can lead to rapid destruction of the brake chopper power components and poses a safety risk due to high current flow.

Complete Troubleshooting Guide

  1. 1

    Immediately de-energize the drive and isolate the brake chopper and resistor circuit.

  2. 2

    Inspect the brake chopper module for any visible signs of damage, burning, or component failure.

  3. 3

    Measure the resistance of the brake resistor and its cabling for any short circuits.

  4. 4

    Verify the wiring between the drive, brake chopper, and resistor for correct connections and absence of shorts to ground.

  5. 5

    Contact ABB service if internal brake chopper failure is suspected after thorough external checks.