80A0
AI supervision
ABB · ACS580 General Purpose Drive
What does 80A0 mean?
An analog input signal has gone outside the predefined minimum or maximum limits. This fault is programmable and prevents the drive from operating with out-of-range sensor feedback, which could lead to incorrect control, erratic behavior, or damage to connected equipment.
Complete Troubleshooting Guide
- 1
Check the actual signal level at the affected analog input (e.g., AI1, AI2).
- 2
Examine the auxiliary code for specific details (e.g., LessMIN, GreaterMAX) if visible on the control panel.
- 3
Inspect the wiring connected to the analog input for breaks, shorts, or interference.
- 4
Review the minimum and maximum limits configured for the input in parameter group 12 Standard AI.