A79C

Brake Chopper IGBT Excess Temperature

ABB · ACS580 General Purpose Drive

What does A79C mean?

The Insulated Gate Bipolar Transistor (IGBT) within the brake chopper has exceeded its internal temperature warning limit. This indicates excessive heat generation due to sustained braking, inadequate cooling, or an overdriven chopper, risking damage to the power components and potentially causing drive failure.

Complete Troubleshooting Guide

  1. 1

    Allow the brake chopper to cool down by stopping operations if possible.

  2. 2

    Check for elevated ambient temperatures in the drive's operating environment.

  3. 3

    Verify proper function of the drive's cooling fan and ensure no airflow obstructions exist.

  4. 4

    Review the sizing and ventilation of the electrical cabinet enclosing the drive.

  5. 5

    Inspect brake resistor overload protection settings (parameters 43.06 to 43.10) for correct configuration.