4313

Motor 2 Temperature Alarm

ABB · ACS800 Standard Firmware

What does 4313 mean?

The measured temperature of motor 2 has exceeded the alarm limit set by parameter 35.05. This indicates a potential overheating condition specific to motor 2, requiring attention to prevent damage.

Common Causes

  • Temperature alarm threshold reached for Motor 2.
  • Motor 2 experiencing excessive heat.
  • Faulty temperature sensor on Motor 2.
  • Overload or inadequate cooling for Motor 2.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the alarm limit value set in parameter 35.05 to ensure it is appropriate for the motor.

  2. 2

    Verify that the actual number of temperature sensors connected to motor 2 corresponds to the value set by the parameter.

  3. 3

    Stop motor 2 and allow it to cool down to a safe operating temperature.

  4. 4

    Ensure proper cooling for motor 2 by checking its cooling fan for operation and cleaning any cooling surfaces.

Browse all codes in this manual (33)
Verified technical data. Last updated: March 2026

Related Faults

Source: ABB ACS800 Standard Firmware