3181
Cross connection
ABB · ACS880 Firmware
What does 3181 mean?
The drive has detected an incorrect connection between the input power cables and the motor cables, specifically if the input power is connected to the motor output terminals. This is a critical wiring error that will trip the drive to prevent severe damage to the power unit and motor due to incorrect voltage application.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Correct any cross connections to prevent irreversible damage to the drive's internal components.
- 4
Before re-energizing, conduct a thorough visual inspection of the drive's output stage and motor for any signs of damage that might have occurred during the fault.