7301

Encoder Error

Allen-Bradley · ABB ACS800 Standard Firmware

What does 7301 mean?

A communication fault exists between the pulse encoder and its interface module, or between the interface module and the drive itself. This prevents accurate speed and position feedback, potentially causing control instability or incorrect motor operation.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Check parameter group 50 (ENCODER MODULE) settings to ensure correct encoder configuration.

Source: ABB ACS800 Standard Firmware
Open Manual (Page 233)