Testxx.FieldPowerOff
Test Channel Field Power Loss
Allen-Bradley · Compact 5000 Digital I/O Modules
What does Testxx.FieldPowerOff mean?
This boolean tag indicates that a field power loss condition exists on the test channel Testxx. A tag value of '1' signifies that the external 24V DC field power supply for the test channel is not present or has failed, disrupting its operation.
Common Causes
- Loss of the 24V DC field power supply connected to the module.
- Blown fuse or tripped circuit breaker in the 24V DC field power supply circuit.
- Improper or damaged wiring between the 24V DC field power supply and the module's field power terminals.
- Failure of the 24V DC field power supply unit itself.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify the 24V DC field power supply connected to the module is energized and producing the correct voltage (e.g., measure 24VDC at the module's field power input terminals).
- 2
Check any fuses or reset any circuit breakers associated with the 24V DC field power supply circuit.
- 3
Inspect the field power wiring connections to the module for integrity and secure termination.
Verified technical data. Last updated: March 2026
Related Faults
Source: Allen-Bradley Compact 5000 Digital I/O Modules