CJChxx.Fault
Cold Junction Data Fault (5069-IY4, 5069-IY4K)
Allen-Bradley · Compact 5000 I/O Analog Modules
What does CJChxx.Fault mean?
This boolean tag indicates that the cold junction data for a specific channel (xx) is inaccurate and cannot be trusted for application use. A value of 1 signifies bad data, causing a fault. The tag automatically resets to 0 once the underlying condition is resolved.
Common Causes
- Cold junction channel (CJChxx) is disabled
- Open Wire condition at the cold junction
- Underrange/Overrange condition for the cold junction temperature
- Short Circuit condition at the cold junction sensor or wiring
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify the channel (CJChxx) is enabled in the module configuration.
- 2
Check for an Open Wire condition at the cold junction sensor or wiring.
- 3
Measure the cold junction temperature to ensure it is within the specified operating range (not underrange or overrange).
- 4
Inspect the cold junction sensor and wiring for any short circuits.
Verified technical data. Last updated: March 2026