Modbus Master Command Response Timeout
Allen-Bradley · Compact 5000 I/O Serial Module
What does I xx .Command yy .ResponseTimeout mean?
This boolean tag indicates that the Modbus master did not receive a response from the slave device within the configured timeout period after sending a specific Modbus command (Command yy). A value of 1 (Occurrence) means the command failed to complete due to the slave's unresponsiveness. This can halt data exchange for that command.
Common Causes
- Modbus slave device is offline, unpowered, or non-responsive
- Incorrect slave address configured for Command yy in the module's command list
- Physical communication line break or severe network congestion
- Timeout value set too low in the module's configuration for the slave's response time
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify the Modbus slave device is powered on, operational, and correctly addressed.
- 2
Check the configured Modbus slave address for Command yy matches the physical slave device's address.
- 3
Inspect the serial communication cable for continuity and proper termination.
- 4
Increase the Modbus command timeout value in the module's configuration if slave response times are slow or variable.