No Access
Allen-Bradley · Logix and SLC PLC
What does F010 mean?
This fault indicates that the system attempted to access a resource or perform an operation for which it lacks authorization. Similar to privilege errors, this prevents unauthorized interaction with the controller or its data.
Common Causes
- User or application attempting to access a protected area without credentials.
- Security permissions configured to deny access to the specific resource.
- Network firewall blocking access to the controller.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify the current user account's credentials and assigned security roles or groups, ensuring it has the necessary privileges for the attempted operation.
- 2
Inspect the PLC's security configuration within Logix Designer or RSLogix 500 (Controller Properties -> Security) to confirm access levels for the resource.
- 3
Check the project file for any embedded security settings, password protection, or project locking mechanisms that may be active.
- 4
Confirm that the communication path (e.g., RSLinx Classic driver, Ethernet configuration) is correctly established and not subject to network security restrictions.