ERR_SOCKET_CONNECT

Socket error during Connect operation

Allen-Bradley · MicroLogix 1400 Programmable Controllers

What does ERR_SOCKET_CONNECT mean?

An error occurred during the socket connect operation. This prevents the Modbus TCP client from establishing a connection to a remote Modbus TCP server, often due to network connectivity problems or incorrect destination settings.

Common Causes

  • Remote Modbus TCP server is unreachable or not listening on the specified port.
  • Network connectivity issues (e.g., cable disconnected, faulty switch, firewall blocking).
  • Incorrect remote IP address or port configured in the Modbus TCP client settings.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the remote Modbus TCP server's IP address and port are correctly configured in the client settings.

  2. 2

    Ping the remote Modbus TCP server's IP address from the controller to check network connectivity.

  3. 3

    Ensure no firewall is blocking the Modbus TCP port (default 502) between the client and server.