Phase VW Short
Allen-Bradley · PowerFlex 4M Adjustable Frequency AC Drive
What does F43 mean?
An excessive current flow, indicative of a short circuit, has been detected between the drive's output terminals V and W. This typically signifies a phase-to-phase short in the motor windings or the cabling, which can cause severe damage to the motor or drive's output stage if not immediately addressed.
Complete Troubleshooting Guide
- 1
Power down the drive and disconnect the motor. Measure resistance between output terminals V and W to check for a short in the motor or cable.
- 2
Inspect the motor power wiring for phases V and W for any signs of physical damage, insulation breakdown, or incorrect connections that could lead to a phase-to-phase short.
- 3
If the motor and wiring are confirmed to be sound, the fault may lie within the drive's power section; consider drive replacement.