F094
Function Loss
Allen-Bradley · PowerFlex 520-series Adjustable Frequency AC Drive
What does F094 mean?
The "Freeze-Fire" (Function Loss) input is inactive or open, typically configured on a digital input terminal. This input is designed to be active during normal operation, and its loss indicates a pre-programmed operational or safety condition that requires the drive to stop.
Complete Troubleshooting Guide
- 1
Ensure the input to the programmed terminal, configured for the 'Freeze-Fire' (Function Loss) function, is closed and active.
- 2
Check all wiring associated with the 'Freeze-Fire' input for continuity, loose connections, or damage.
- 3
Verify the programming of the digital input (e.g., t062-t068 parameters) to confirm it is correctly assigned and configured.