24
Decel Inhibit
Allen-Bradley · PowerFlex 700 AC Drives
What does 24 mean?
The drive is not following a commanded deceleration because it is attempting to limit bus voltage. This indicates the DC bus voltage is rising due to regenerative energy, potentially exceeding safe limits and causing the drive to inhibit deceleration.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Disable bus regulation and/or add a dynamic brake resistor and/or extend the deceleration time parameter.
Source: Allen-Bradley PowerFlex 700 AC Drives
Open Manual (Page 85)