10138

I1 Powering Down

Allen-Bradley · PowerFlex 750 AC Drive

What does 10138 mean?

This fault is asserted when the DC bus voltage drops to 80% of its rated value on port 1. This indicates a significant loss of DC bus voltage which can lead to drive shutdown and loss of control.

Complete Troubleshooting Guide

  1. 1

    Measure the DC bus voltage to confirm it is indeed dropping to 80% of its rated value during operation.

  2. 2

    Check the incoming AC power supply for stability, proper voltage levels, and ensure no phase loss is occurring.

  3. 3

    Inspect the DC bus capacitors for any signs of degradation, bulging, or leakage that would indicate reduced capacitance.

  4. 4

    Verify the proper operation of the drive's power supply monitoring circuitry to ensure accurate voltage readings.

  5. 5

    Reduce the drive load if the powering down event frequently correlates with high load conditions on the motor.