Phase UNegToGrnd
Allen-Bradley · PowerFlex 750 AC Drive
What does 44 mean?
A phase-to-ground fault has been detected between the drive and the motor on output phase U, specifically identifying a negative voltage transient or specific ground path. This indicates insulation breakdown or a short from output phase U to earth. This condition can damage the drive and motor if not quickly addressed, and poses an electrical safety risk.
Complete Troubleshooting Guide
- 1
Rotate the U/T1, V/T2, W/T3 motor connections at the drive. If the problem follows the wire (e.g., now a VNegToGrnd fault), suspect a field wiring problem or a motor winding fault.
- 2
If the fault remains on phase U after rotating connections, suspect a problem with the drive's output stage for phase U.
- 3
Measure the insulation resistance of the motor windings and the motor cable to ground using a megger. Expect values greater than 1 MΩ.