F016

Scanner not available for 1771 rack adapter

Allen-Bradley · Logix 5000

What does F016 mean?

The scanner is not available to communicate with a 1771 rack adapter. This disrupts I/O communication with the specified rack.

Common Causes

  • The scanner is not available to communicate with a 1771 rack adapter

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Measure supply voltage at the 1771 rack adapter's power input terminals against specified nominal voltage.

  2. 2

    Inspect the RIO (Remote I/O) cable connecting the Logix 5000 system to the 1771 rack adapter for damage and secure connections at both ends.

  3. 3

    Verify the RIO configuration parameters within the Logix 5000 program (e.g., rack number, baud rate, module type) match the physical 1771 rack adapter settings (e.g., DIP switches).

  4. 4

    Observe the status indicator LEDs on the 1771 rack adapter for any fault or communication errors, referring to the adapter's manual for interpretation.

  5. 5

    Inspect the 1771 rack adapter for proper seating in its slot within the 1771 chassis, ensuring all backplane connectors are fully engaged.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults