42EC

GROUPERR_RANGE_OVERRIDECHANGETIME

Beckhoff · TwinCAT 2 NC

What does 42EC mean?

The 'Override Change Time' parameter configured for the group is outside its allowed range of (0.0 ... 1000.0] seconds. This parameter controls the ramp rate or filter time when an override value is changed, and an invalid setting can result in abrupt motion changes, jerky movements, or delayed override responses.

Complete Troubleshooting Guide

  1. 1

    Set the 'Override Change Time' parameter in the group's NC configuration to a value strictly greater than 0.0 and up to 1000.0 seconds.

  2. 2

    Tune this parameter carefully to achieve smooth and responsive override behavior without causing instability.

  3. 3

    Save configuration changes and restart the NC system.