Fatal Error (Safety Technology Initialization)
Bosch Rexroth · IndraDrive C Drive Controllers
What does F8203 mean?
This is a fatal error specifically tied to the drive's safety technology during initialization. When F8203 occurs, the closed-loop or open-loop U/f control of the drive is no longer guaranteed. The drive immediately switches off, becoming torque-free, overriding settings in P-0-0119 and P-0-0117. This error requires a complete recommissioning of the safety technology.
Common Causes
- An error condition detected within the drive's safety technology system during initialization.
- Safety technology requires complete recommissioning.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Switch the drive off completely.
- 2
Recommission the safety technology completely.
- 3
Clear the error message using command S-0-0099 (C0500 Reset class 1 diagnostics). This may require switching to parameter mode or a complete drive power cycle.
- 4
Ensure the drive is in operating mode and power is switched on ("Ab").
- 5
Switch on drive enable again (0-1 edge).
- 6
If this fatal error recurs repeatedly, replacement of an entire component (e.g. motor or drive controller) may be necessary.