5
Voltage warning high
Danfoss · VLT 2800 Variable Speed Drive
What does 5 mean?
The DC bus voltage (VDC) has exceeded the 'Voltage warning high' limit. The motor continues to operate, but if the VDC remains high for 5-10 seconds, the inverter will trip with an Alarm 7 (Overvoltage). This can be caused by an excessively high supply voltage or fast motor deceleration with insufficient braking.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
If overvoltage persists during deceleration, consider installing a braking resistor or braking chopper.
Source: Danfoss VLT 2800 Variable Speed Drive