17
Control word timeout
Danfoss · VLT AutomationDrive FC 301/302
What does 17 mean?
No communication is detected from the control word source to the frequency converter. This warning is active only when parameter 8-04 Control Word Timeout Function is not set to [0] Off. If set to [5] Stop and trip, the drive will ramp down to a stop and issue an alarm.
Complete Troubleshooting Guide
- 1
Check the physical connections of the serial communication cable for integrity and proper seating.
- 2
Increase the timeout duration set in parameter 8-03 Control Word Timeout Time.
- 3
Verify the proper operation and functionality of the external communication equipment (e.g., PLC, HMI).
- 4
Confirm that proper EMC (Electromagnetic Compatibility) installation guidelines were followed to prevent communication interference.