Live zero error
Danfoss · VLT AutomationDrive FC 301/302
What does 2 mean?
This warning/alarm appears if programmed in parameter 6-01 Live Zero Timeout Function. It indicates that the signal on one of the analog inputs is less than 50% of its programmed minimum value, typically caused by broken wiring or a faulty signal-sending device.
Complete Troubleshooting Guide
- 1
Check connections on all analog mains terminals (control card 53/54/55, VLT GIO MCB 101 terminals 11/12/10, VLT AIO Option MCB 109 terminals 1/3/5/2/4/6).
- 2
Verify that the drive programming and switch settings match the analog signal type being used.
- 3
Perform an input terminal signal test to diagnose the analog input circuit.