ALARM 46
Gate drive voltage low
Danfoss · VLT HVAC Basic FC 101
What does ALARM 46 mean?
The supply voltage on the power card, which generates 24 V, 5 V, and ±18 V, is out of range. This indicates a problem with the switch mode power supply (SMPS) on the power card, affecting the drive's ability to control the motor's power transistors.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
If the issue persists, the power card may need replacement.