1

10 Volts low (control card)

Danfoss · VLT HVAC Drive FC 102

What does 1 mean?

The control card voltage from terminal 50 is less than 10 V, indicating an overload on the 10 V supply (maximum 15 mA or minimum 590 Ω). A short circuit in a connected potentiometer or incorrect wiring can cause this condition. This can lead to unreliable sensor readings or control circuit operation.

Source: Danfoss VLT HVAC Drive FC 102